15. ALARMS AND TROUBLESHOOTING
15.1 Alarm summary table
When an alarm is activated a message identifying the alarm is displayed on the control module.
In the case of potentially dangerous alarms, the control module automatically shuts the humidifi er down.
For some alarm events (see Table 15.a), the signalling of the alarm is accompanied by the activation of
an alarm relay, as described in: Other auxiliary contacts.
If the cause of the alarm is no longer valid, the humidifi er and alarm relay output can be reset automati-
cally or manually, according to the type of problem, while the message displayed is deactivated manually
by pressing the reset-PRG button.
If no longer active, the alarm status continues to be indicated until the reset-PRG button is pressed.
Still active alarms can not be reset.
In the type C control module the presence of an alarm is indicated by the lighting up of LED 9 and
a combination of the LEDs 5 (Fig. 15.a); in the event of more than one alarm, these are indicated in
sequence, at 2 second intervals.
In the type H or T control module, if not in programming phase, in the presence of an alarm LED 9 (see
fi g. 15.b) begins fl ashing, while the display 5 indicates the alphanumeric alarm code.
The message is displayed cyclically, for a duration of two seconds, alternating with the measurement
normally displayed (if the measurement normally displayed corresponds to a disconnected probe, the
measurement is not displayed; this will automatically return to the display if the probe is reconnected).
In the event of more than one alarm, the display indicates all the corresponding codes in sequence, at
two second intervals.
The alarm Ec cannot be reset.
In the event of the alarm CL (regular maintenance required), the alarm can be reset only by resetting the
hour counter; see Resetting the hour counter.
The alarm E1 may appear in two distinct cases:
1. Malfunction when reading from the parameter memory (typically on start-up)
The default parameters are temporarily recalled, without being saved in the parameter memory (the
parameters can be accessed and the correct values restored).
In any case the default parameter recall procedure is recommended; see Recalling the default
parameters.
2. Malfunction when writing to the parameter memory (typically on pressing the PRG button)
Any modifi cations made will be cancelled; the parameters can be accessed, the values modifi ed and
save operation repeated.
Table 15.a lists the alarm indications, the causes, the conditions and the possible solutions.
The remote terminal column indicates the alarm message that appears on the LCD display of the CAREL
Humivisor remote control panel, if one is connected to the humidifi er.
code displayed
H and T
controller
C controller CAREL
Humivisor
remote
terminal
cause solution
( once having tried the suggestion, if the problem
persists, contact the CAREL service department)
action reset alarm
relay
alarm
30% 50% 75% 100%
1234
E202 •activation of safety
thermostat
• Klixon activation
•the thp output is open
- check the earth current of the heaters, and if replace
necessary.
- manually reset the Klixon
- problem dependent mainly on operation without water;
- turn the machine off and, once it has cooled
down, reactivate the thermostat on the cylinder cover
after having cleaned the cylinder and the level control,
checking the effi ciency of the components;
- check that the electrical and water connections are in
order and that the machine is supplied correctly;
- it may be necessary to replace the PTC sensors if installed
not available active
if Et
remain
in order
at least
a
minute.
alarm
30% 50% 75% 100%
1234
E204 contradiction of the fl oat - check the correct supply of water to the cylinder;
- turn the machine off and clean: the cylinder, the level
control and the fi ll electrovalve
see procedure
“AR”
manual only
if EE
appears
during
AR
non previsto E205 high conductivity of the
supply water
- turn the machine off and clean the water conductivity
measuring electrodes;
- if the problem persists, change the source of the supply
water or install a suitable treatment system (demineralisa-
tion, even partial);
- the problem will not be resolved by softening the supply
water
total shutdown auto
available
active
Fig. 15.a
Fig. 15.b